0
<-- nev left start -->

Power Monitoring Current Sensor

Power Monitoring Current Sensor
Power Monitoring Current Sensor
Price And Quantity
  • Piece/Pieces
  • 10
  • Piece/Pieces
  • 1.00-
    Product Description

    RTO500K1 series dismountable hall effect current sensor is a open loop device based on the measuring principle of the hall effect ,with a galvanic isolation between primary and secondary circuit,it provides accurate electronic measurement of DC,AC or pulsed currents

    Electrical  data(Ta=25±5℃,RL=2KΩ ,CL=10000PF) 

    Type /Parameter

    RTO30K1

    RTO50K1

    RTO100K1

    RTO200K1

    RTO300K1

    RTO400K1

    RTO500K1

    Rated current(Ipn)

    ±30

    ±50

    ±100

    ±200

    ±300

    ±400

    ±500

    Measuring range(Ip)

    ±60

    ±100

    ±200

    ±400

    ±600

    ±800

    ±1000

    Rated output

    @Ip=±Ipn

     

    ±4±1%

     

     

     

    Supply voltage

    ±15±5%

    Power Consumption

    +25,-10

    Offset voltage

    @Ip=0

     

    ±20

     

     

     

    Magnetic offset

    @Ip=±Ipn-0

     

    ±20

     

     

     

    Offset drift

    @ -40~+85℃

     

    ≤±1

     

     

     

    output drift

    @ -40~+85℃

     

    ≤±1

     

     

     

    Linearity

    @Ip=0-±Ipn

     

    ≤1

     

     

     

    Response time

    @50A/μ S, 10%-90%

     

    ≤5

     

     

     

    Galvanic isolation

    @ 50HZ,AC,1min

     

    2.5

     

     

     

    Isolation resistance

    @ DC 500V

     

    1000

     

     

     

    Application

     

    • Variable speed drives
    • Welding machine
    • Battery supplied applications
    • Uninterruptible Power Supplies (UPS) 
    • Electrochemical

    General  date

     

    Value

    Unit

    Symbol

    Operating temperature

    -40 to +85

    ºC

    TA

    Storage temperature

    -40 to +125

    ºC

    TS

    Mass(approx)

    72

    g

    M


    Directions  for  use

    • When the current will be measured goes through a sensor, the voltage will be measured at the output end.
    • (Note: The false wiring may result in the damage of the sensor)
    • Custom design in the different rated input current and the output voltage are available.

    Standard

    • UL94-V0. ;EN60947-1:2004 ;IEC60950-1:2001
    • EN50178:1998 ;SJ 20790-2000

     



     

    Trade Information
    • 20000 Per Month
    • 15 Days
      Contact Us

      Room 1123-1127,No.81 South QinZhou Road, XuHui Shanghai Shanghai China 86-21-64516109
      Phone :+8618001811078